Containerised Substation 1.5MVA

Containerised 1.5MVA Substation with 3200A Board

  • 1 x Lucy Aegis IBB RMU includes:
    • 24VDC Remote motors on circuit breaker only
    • Fanox Protection Relay 
    • Contrel Earth Leakage on all circuit breakers
  • 1 x Grant Transformers ANAF Cast resin 1.5MVA 11kV/415V Transformer Includes:
    • Voltage Range: +/- 2 x 2.5% Tap changer (5 position off load tap changer)
    • PT100 Probes 
    • Temperature Relay
  • 1 x ELSTEEL U-Shaped 2500A Distribution Board Includes:
    • 1 x ABB 2500 3P 100kA Auto ACB  
    • 2 x ABB 630A 4P 70kA Circuit Breakers includes:
      • High Terminal Touch protection
      • External handle kit 
      • Bolt on adjustable earth leakage 
      • 24V Shunt trip 
      • Electronic Overload adjustable to 40% of rated current ( 630A-252A)
    • 2 x ABB 400A 4P Circuit Breakers includes:
      • High Terminal Touch protection
      • External handle kit 
      • Bolt on adjustable earth leakage 
      • 24V Shunt trip 
      • Electronic Overload adjustable to 40% of rated current ( 400A-160A)
    • 7 x ABB 250A 4P Circuit Breaker Includes: 
      • High Terminal Touch protection
      • External handle kit 
      • Bolt on adjustable earth leakage 
      • 24V Shunt trip 
      • Electronic Overload adjustable to 40% of rated current ( 250A-100A)
    • 1 x Weidmuiller 24VDC UPS System with 17AH Battery 
    • Control Cubicle for remote switching of HV Circuit breakers 
    • ABB Indicator lights and Push buttons
  • 1 x White 20Ft cotnainerised switch room includes:
    • Lined with 50mm Refrigeration panel 
    • Internal division walls to create 3 separate areas:
      • HV Switch room
      • Transformer bay 
      • LV Switch room 
    • Includes 2 x PA Doors into LV Switch Room 
    • Internal LED Lighting with battery back up for emergency lighting 
    • Emergency Exit lighting above doors
    • Internal Fire detection and external alarm and strobe (Not back to base system)
    • HV switch Room accessible via 2 x External container doors 
    • Vinyl flooring through out 
    • Louvres in transformer bay for natural cooling
    • Small Light and Power DB with 1 x 10A GPO in LV switch room

Available for Hire or Sale

Group: 2974


Enquire about this Product